Permit Information
Permit NumberELE08-02536
StatusFinaled
Name COMMERCIAL ELECTRIC
Site Address 1609 S OWYHEE ST
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: Provide and install switchboard, panelboards, disconnects, transformer, lighting fixtures, receptacles and switches.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/2/200912/3/200912/3/2009APASS
DetailsBob Reichert
Requesting an inspection of the dental office area for final. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ul verified x-ray machines ok, ok to final, signed occupancy card
Final10/23/200910/26/200910/26/2009APART
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to final all but x-ray machines, see correction notice, signed t/o card
Electrical Rough-In10/23/200910/23/200910/23/2009APASS
DetailsBob Reichert
Requestig a inspection of the Dentist office. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to cover ceilings only, left correction notice for x-ray machines, BCC 4-05-033(A),(B) all equipment shall be listed by a nationally recognized testing laboratory, NEC 110.3 all equipment shall be approved
Electrical Rough-In9/30/20099/30/20099/30/2009PPASS
DetailsBob Reichert
Requesting a re inspection of the dental office. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty walls only ok to cover
Electrical Rough-In9/28/20099/29/20099/29/2009PCANC
DetailsBob Reichert
Requesting an inspection of the Dental office. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty see conference
Conference9/29/20099/29/20099/29/2009PDONE
DetailsBob Reichert
Requesting an inspection of the Dental office. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty met electrican, reviewed patient care areas and the requirement for redundant grounding, not using fmc for redundant grounding, can't add esc inspection
Conference9/1/20099/1/20099/1/2009PCANC
DetailsBob Reichert
Requesting a undergound conduit inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty wrong type request, see ri
Electrical Rough-In9/1/20099/1/20099/1/2009PPASS
DetailsBob Reichert
Requesting a undergound conduit inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty contractor opened u/g , ok to cover u/g to 6 lights
Electrical Rough-In8/31/20098/31/20098/31/2009PPART
DetailsBob Reichert
Requesting inspection of 6 pole bases. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to pour pole bases only, contractor to uncover u/g to inspect for conduit bends, backfill material, conduit depth, spacing
Final8/11/20098/12/20098/12/2009APART
DetailsBob Reichert
Requesting a late morning final inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to part final, signed t/o card, left correction notice- dental area shall not be placed into service, will resolve and call for final later
Final8/10/20098/11/20098/11/2009APART
DetailsBob Reichert
Requesting a final inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty looked at mezzanine, rooftop, and outside, anop, need to see pump house before t/o, told contractor will check with 315
Final8/10/20098/10/20098/10/2009APART
DetailsJack Frank
Requesting a final inspection. Phone #: ###-#### Internet Inspection Request from: Dan area B anop
Final8/7/20098/7/20098/7/2009PPART
DetailsJack Frank
Requesting a partial final inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty t/o for d wing anop
Final8/6/20098/7/20098/7/2009APART
DetailsJack Frank
Requesting a partial final inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty A wing and administration area ok anop for T/O
Electrical Rough-In8/6/20098/7/20098/7/2009ANR
DetailsJack Frank
Requesting a ceiling inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty note art 225, for more than one service to outbuilding, and 250.32 electrode for bld
Electrical Rough-In8/6/20098/6/20098/6/2009PCANC
DetailsJack Frank
Requesting a partial final inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty wanted partial final check two areas not ready needs power on and all recepts working
Electrical Rough-In7/28/20097/28/20097/28/2009PPART
DetailsBob Reichert
Requesting a partial ceiling inspection to cover.
Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ceilings ok to cover music room and south c wing except dental area anop
Electrical Rough-In7/24/20097/27/20097/27/2009APART
DetailsBob Reichert
Requesting a ceiling inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to cover ceilings sw part "D" wing anop
Electrical Rough-In7/16/20097/16/20097/16/2009APASS
DetailsBob Reichert
Requesting a soffit inspection for the East and South entry. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty east and south soffits ok to cover
Electrical Rough-In7/13/20097/13/20097/13/2009PPART
DetailsBob Reichert
Requesting a soffit inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to cover soffits anop
Electrical Rough-In7/9/20097/9/20097/9/2009PPART
DetailsDoug A Poedy
Requesting an inspection of A wing ceiling to close for cover. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty. Ok to cover south A area and related corridors ceilings.
Electrical Rough-In7/1/20097/1/20097/1/2009PPART
DetailsJack Frank
Requesting a ceiling inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok anop
Electrical Rough-In6/24/20096/24/20096/25/2009PPART
DetailsJack Frank
Requesting an inspection to close for cover C wing administration ceiling, and reinspection of D wing ceiling. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok anop
Electrical Rough-In6/16/20096/16/20096/16/2009PFAIL
DetailsJack Frank
Requesting a ceiling inspection to cover for D wing. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty
corr called needs support wires for cables and boxes
Electrical Rough-In6/8/20096/9/20096/9/2009APART
DetailsBob Reichert
Requesting a partial ceiling inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to cover ceilings anop
Conference6/5/20096/8/20096/8/2009ADONE
DetailsJack Frank
Requesting a consultation. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty conf. on wiremold
Electrical Rough-In5/27/20095/27/20095/27/2009PPASS
DetailsJack Frank
Requesting an interior wall inspection for the dentist office and C wing. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok anop
Electrical Rough-In5/20/20095/20/20095/21/2009PPART
DetailsJack Frank
Requesting an inspection of the interior walls in B wing. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty
ok anop
Electrical Rough-In5/7/20095/7/20095/7/2009PPART
DetailsBob Reichert
Requesting a rough in inspection of B wing exterior walls. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty walls and ceilings ok to cover anop
Electrical Rough-In4/30/20094/30/20094/30/2009PPART
DetailsBob Reichert
Requesting an inspection of the high ceiling in B wing and a service inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to cover high ceiling anop only
Permanent Service4/30/20094/30/20094/30/2009PPASS
DetailsBob Reichert
Requesting an inspection of the high ceiling in B wing and a service inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty p/s u/g n ok, sticker is on main service gear
Electrical Rough-In4/23/20094/23/20094/23/2009PPART
DetailsJack Frank
Requesting a wall inspection for the Library and the end of A wing. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok anop
Conference4/14/20094/14/20094/14/2009ADONE
DetailsBob Reichert
talked about solar array installation for school
Electrical Rough-In4/9/20094/9/20094/9/2009PPASS
DetailsBob Reichert
Requesting a wall inspection for C wing. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty c wing walls only ok to cover anop
Electrical Rough-In4/8/20094/8/20094/8/2009PPART
DetailsMike Kinnear
Requesting a wall inspection for A wing. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok cover walls anop
Electrical Rough-In3/31/20093/31/20093/31/2009APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 3/31/2009 at 6:34:56 AM. Contact: ###-####. walls only ok to cover anop
Electrical Rough-In3/24/20093/24/20093/24/2009PPART
DetailsBob Reichert
Requesting a high ceiling inspection of the Library and the end of A wing. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to cover library and part of A wing high ceilings anop
Electrical Rough-In3/18/20093/19/20093/19/2009APART
DetailsMike Kinnear
Requesting an exterior wall inspection for C wing. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok cover ext walls only anop
Electrical Rough-In3/16/20093/16/20093/16/2009APART
DetailsMike Kinnear
Requesting an inspection of C wing corridor and above the 12'' deck ceiling. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok cover hard lid fire ceiling anop
Electrical Rough-In3/10/20093/11/20093/11/2009APASS
DetailsMike Kinnear
Requesting a rough in inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok cover walls & hard lid ceilings anop
Electrical Rough-In2/27/20093/2/20093/2/2009APASS
DetailsBob Reichert
Requesting a wall inspection for A wing. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty corrections made, ok to cover walls only area A, anop
Electrical Rough-In2/27/20092/27/20092/27/2009PFAIL
DetailsBob Reichert
Requesting a wall inspection for A wing. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty met contractor, gave correction notice, NEC 358..26 there shall not be more than 360 degrees bend in raceway , 358.30(A) emt shall be securely fastened within 3' of every termination, BCC all boxes shall be completed with conduit run to them, will call for re-inspection next week early
Electrical Rough-In2/16/20092/17/20092/17/2009APASS
DetailsBob Reichert
Requesting a ceiling inspection for D-wing. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to cover D wing hard lids only anop
Electrical Rough-In2/5/20092/6/20092/6/2009APART
DetailsBob Reichert
Requesting a firewall inspection in "A" wing. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty met general and electrical contractor, ok to provide 1 side for firewall and part hall- top 1/2 cover only
Electrical Rough-In1/30/20092/2/20092/2/2009APART
DetailsBob Reichert
Requesting a ceiling inspection only for A-wing. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to cover under deck only anop
Electrical Rough-In11/12/200811/13/200811/13/2008PPART
DetailsBob Reichert
Requesting an early afternoon underground inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to cover u/g anop for computer desks and dental area ( power in rigid conduit )
Electrical Rough-In11/4/200811/5/200811/5/2008APART
DetailsMike Kinnear
Requesting an inspection of slab work. Our man Scott will be there. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok cover under ground conduit & boxes anop
Electrical Rough-In10/15/200810/15/200810/15/2008PPART
DetailsBob Reichert
Requesting a partial underground inspection of the parking lot. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty u/g anop ok to cover- west and north parts of building
Electrical Rough-In10/8/200810/9/200810/9/2008APART
DetailsBob Reichert
Requesting a partial underground inspection of the parking lot. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty east and south u/g anop ok to cover
Electrical Rough-In10/1/200810/1/200810/1/2008PPART
DetailsBob Reichert
Requesting a partial underground and light pole bases inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to cover lv, power, communications interior under building for area C
Electrical Rough-In9/23/20089/24/20089/24/2008APART
DetailsBob Reichert
Requesting a partial underground inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok to cover stem walls east of transformer, ok to cover u/g duct north of transformer to elect room about 120 feet north, looked at block-outs east stem walls
Electrical Rough-In9/15/20089/16/20089/16/2008APART
DetailsMike Kinnear
Requesting a UFER and partial underground inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty ok cover ufer ground part duct bank to transformer