Final | 10/3/2008 | 10/3/2008 | 10/3/2008 | P | PASS |
Bob Reichert
|
|
|
ROBERT Phone #: ###-#### corrections made, ok to final, no esc this project
|
Final | 10/1/2008 | 10/1/2008 | 10/1/2008 | P | FAIL |
Jack Frank
|
|
|
robert Phone #: ###-#### corr meet contr, 110.3(B) manufacture's state no load conducters shall exit top endwall of p/s panel contr altered panel and exited the top endwall
|
Permanent Service | 9/30/2008 | 9/30/2008 | 9/30/2008 | P | PASS |
Bob Reichert
|
|
|
ROBERT ###-#### look at final for sunlight res on mast wire and roof clearance, blocks in front of panel for depth of working space, rest ok, p/s o/h rec ok, no esc this project
|