Final | 11/4/2008 | 11/6/2008 | 11/6/2008 | A | PASS |
Bob Reichert
|
|
|
butch Phone #: ###-#### ok to final
|
Electrical Rough-In | 10/7/2008 | 10/8/2008 | 10/8/2008 | A | PASS |
Bob Reichert
|
|
|
butch Phone #: ###-####called left message left survey, NEC 210.52(D) shall provide receptacle within 3' of bath sink, 210.11(C)(3) bath receptacle shall be supplied by 20a circuit with no other outlets, 210.52(A)(1) receptacle shall be installed such that no point is over 6' from receptacle in wall line, ric ok, no green sticker left, talked with contractor
|