Permit Information
Permit NumberELE08-02689
StatusFinaled
Name CITYLIGHT ELECTRIC LLC
Site Address 3896 N WOODY LN
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: electrical including, service, outlets, switches, lights in new building INCLUDING DOWN STAIRS GARAGE
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/30/20094/30/20094/30/2009PPASS
DetailsPat Lass
Rick Phone #: ###-####
Final4/29/20094/30/20094/30/2009AFAIL
DetailsJack Frank
Rick Phone #: ###-#### Internet Inspection Request from: Rick Beckman corr called 314.3 no metallic allowed in plastic boxes floor bos upstairs din rm
Final4/29/20094/29/20094/29/2009PFAIL
DetailsJack Frank
Rick Phone #: ###-#### Internet Inspection Request from: Rick Beckman called corr, 210.52(A&B) needs outlet for wall space in din. rm. shall be on SABC top of stairs, 314.17 (A&B) needs connectors for cables at wirmold boxes, 110.3(A) outlet M bed rm. between doors no power
Electrical Rough-In4/20/20094/21/20094/21/2009ACANC
DetailsPat Lass
suspended ceiling inspection only Phone #: ###-#### Internet Inspection Request from: Rick Beckman
this is for the residential portion
Permanent Service2/25/20092/26/20092/26/2009APASS
DetailsPat Lass
Phone #: ###-#### Internet Inspection Request from: Rick Beckman

P/S U/G N Ok
Electrical Rough-In2/10/20092/10/20092/10/2009PPART
DetailsPat Lass
r/i & grounding -- Rick ###-####
electrode ok
Electrical Rough-In2/3/20092/4/20092/4/2009APASS
DetailsPat Lass
###-#### -
told Rick that outside feeder has the same rule as a service for the length of pipe we allow to main disconnect
R/I Ok
Electrical Rough-In1/20/20091/21/20091/21/2009APASS
DetailsMike Kinnear
###-#### ok cover soffit ri only note esc permit on parcel hold
Electrical Rough-In1/20/20091/20/20091/20/2009PFAIL
DetailsJack Frank
rick ###-#### Note: please call for instruction called wiring covered before inspection, address emergency ballast mounted on combustible material
Electrical Rough-In10/20/200810/21/200810/21/2008APASS
DetailsJim Schmer
underground - mike - ###-#### - rick w/citylight will be out of town - conduits are marked 2 panel
Conference10/2/200810/3/200810/2/2008ACANC
DetailsPat Lass
call 1/2 hour before inspection Phone #: ###-#### Internet Inspection Request from: Rick Beckman Inspection cancelled from web by: Rick Beckman