Final | 1/21/2009 | 1/22/2009 | 1/22/2009 | A | PASS |
Bob Reichert
|
|
|
suire A Phone #: ###-#### Internet Inspection Request from: Dan Surerus met contractor, ok to final, no esc this project
|
Final | 1/21/2009 | 1/22/2009 | 1/21/2009 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Surerus Inspection cancelled from web by: Dan Surerus
|
Rough-In Permanent Service | 10/6/2008 | 10/7/2008 | 10/7/2008 | A | PASS |
Bob Reichert
|
|
|
Suite A Phone #: ###-#### Internet Inspection Request from: Dan Surerus corrections made, ric ok, p/s, exst meter pak, n, ok, no esc this project
|
Rough-In Permanent Service | 10/3/2008 | 10/6/2008 | 10/6/2008 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Surerus called contractor, left corredction notice, NEC 300.4(A)&(D) edge of bored holes and mc cable shall be 1 1/4" from edge of framing members, 110.26(F)(1)(b) shall provide drip protection for foreign systems over and above dedicated space over panels, BCC shall provide permit for each meter and identify panel and main meter, approved set of plans shall be on job, no esc this project
|