Final | 12/2/2008 | 12/3/2008 | 12/3/2008 | A | PASS |
Bob Reichert
|
|
|
michelle Phone #: ###-#### met owner, corrections made ,ok to final
|
Final | 12/2/2008 | 12/2/2008 | 12/2/2008 | P | NR |
Bob Reichert
|
|
|
michelle Phone #: ###-#### called corrections not done
|
Final | 12/1/2008 | 12/2/2008 | 12/2/2008 | P | FAIL |
Bob Reichert
|
|
|
Michelle Phone #: ###-#### called, left correction notice, NEC 348.12(1) fmc shall not be used in wet locations and conductors must be suitable for wet locations, 210.52(D) shall install gfci protected receptacle within 3' of bath basin, 210.11(C)(3) there shall be no other outlets on bath circuit, 110.3(B) listed equipment shall be installed and used in accordance with labels and operate- garage entry area, 314.21 shall repair all drywall around boxes- less than 1/8" gap at u/c lights and range receptacle, 410.16(C) shall provide minimum 12" from edge of storage space to edge of fixture in clothes closet- master bed room, 680.73 tub access shall be per manufacturers instructions and accessible without removing screws or other permanent finish, 250.94 intersystem bonding terminination shall be provided
|
Conference | 12/1/2008 | 12/1/2008 | 12/1/2008 | P | DONE |
Bob Reichert
|
|
|
michelle - conference - later afternoon please Phone #: ###-#### told owner if ready for final, needed to finish all work and call in for inspection
|
Electrical Rough-In | 10/29/2008 | 10/30/2008 | 10/30/2008 | P | PASS |
Bob Reichert
|
|
|
bill Phone #: ###-#### ric ok
|
Permanent Service | 10/30/2008 | 10/30/2008 | 10/30/2008 | P | PASS |
Bob Reichert
|
|
|
bill Phone #: ###-#### p/s u/g n ok
|
Electrical Rough-In | 10/22/2008 | 10/23/2008 | 10/23/2008 | A | NR |
Bob Reichert
|
|
|
bill/david Note: please call 1/2 hr prior to inspection Phone #: ###-#### see conference
|
Conference | 10/23/2008 | 10/23/2008 | 10/23/2008 | A | CANC |
Bob Reichert
|
|
|
bill/david Note: please call 1/2 hr prior to inspection Phone #: ###-#### called, left message, they asked for framer to take notes, reviewed grounding, outlet spacing, make-up, 1 1/4", stapling, all work to be installed, boxes flush with finished surface, abrasion protection, outlets placement front and back of building, access required for LB behind panel, suggested to wire without LB, 6" free conductor length, told only owner can wire building, circuiting for outside receptacles not to be on dining room circuit, and to be gfci protected. Called owner, told he could see on-line the items discussed.
|
Conference | 10/8/2008 | 10/9/2008 | 10/9/2008 | A | DONE |
Bob Reichert
|
|
|
David ###-#### reviewed service, sub-panels, outlet spacing, no screws in boxes, 1 1/4", free length of conductor and when to call for ri
|