Permit Information
Permit NumberELE08-02758
StatusFinaled
Name CHRISTOPHER SODERLUND
Site Address 3008 W GRACE ST
Project Name 
Customer Number 
ePlanReview 
Description
see attached sheet
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/21/20101/21/20101/21/2010PPASS
DetailsBob Reichert
Chris Phone #: ###-#### corrections made, ok to final
Final1/19/20101/19/20101/19/2010PFAIL
DetailsDoug A Poedy
chris Phone #: ###-####. 210.8 GFCI Kitchen
Final1/12/20101/12/20101/12/2010PPART
DetailsBob Reichert
Christopher Phone #: ###-#### met helper, not really ready, needs to add recpt at bottom of stairs, put on panel covers, label panels, bond hot and cold water pipes, run nm cable in flex at hot water heater, add blank cover in ceiling, check open n for kitchen gfci, add receptale upper room with arched doors, add recpt cover, add bushings to low volt media cables, add recpt cover in media panel, do rooftop receptacles with in-use covers, ground metal boxes, check rest of rooftop
Electrical Rough-In11/19/200911/19/200911/19/2009PCANC
DetailsDoug A Poedy
Christopher Phone #: ###-####. Partial final so that they could install appliances.
Final11/19/200911/19/200911/19/2009PPART
DetailsDoug A Poedy
Christopher Phone #: ###-####. Checked both laundry(stacked units) receptacles, behind zero air refrigerator receptacle, and notified to hard wire double oven.
Permanent Service4/14/20094/15/20094/14/2009APASS
DetailsPat Lass
christopher - please call for access Phone #: ###-####
P/S U/G N Ok
Permanent Service4/8/20094/9/20094/9/2009ANR
DetailsJack Frank
Phone #: ###-#### called needs #4 copper for GEC from each panel to electrode, needs to install u/g conduit into meterbase
Electrical Rough-In3/24/20093/25/20093/24/2009APASS
DetailsPat Lass
nels Phone #: ###-####
R/I ok
check for required receps on final because approved plan not followed and incomplete
Electrical Rough-In3/23/20093/23/20093/23/2009PFAIL
DetailsPat Lass
Nelson Phone #: ###-####
derate wires more than 9 through a hole.
210.52
Electrical Rough-In3/19/20093/20/20093/20/2009PFAIL
DetailsPat Lass
nelson Phone #: ###-####
replace boxes that have extra knock-outs missing. box overfilled. wiring in cold air return. no more than 9 current carying conductors through a hole. will have to insure that all required receps are installed on final because plan is unclear.
Conference3/16/20093/17/20093/17/2009APART
DetailsPat Lass
Chris- After 10 please- call 30 mins prior to going Phone #: ###-####
talked about general requirements.
Electrical Rough-In3/16/20093/16/20093/16/2009PFAIL
DetailsJack Frank
brian Phone #: ###-#### do not cover posted owner needs to be present at time of inspection, needs conference, borken boxes, box fill outlet spacing walls and counters grding at p/s wrong, plans do not match job, have no idea if he has required circuits for kit, bath, and so on, phone number in notes was for framer,