Final | 11/21/2008 | 11/24/2008 | 11/24/2008 | A | PASS |
Mike Kinnear
|
|
|
Lock box code 1290, if you have any questions, please call Clay. Thank You. Phone #: ###-#### Internet Inspection Request from: Clay Morgan ok final
|
Rough-In Permanent Service | 11/3/2008 | 11/3/2008 | 11/3/2008 | P | PASS |
Pat Lass
|
|
|
If you have any questions, please call Clay, Thank You. Phone #: ###-#### Internet Inspection Request from: Clay Morgan P/S O/H R Ok R/I Ok
|
Rough-In Permanent Service | 10/31/2008 | 11/3/2008 | 11/3/2008 | A | FAIL |
Bob Reichert
|
|
|
House will be open, if you have any questions, please call Clay. Thank You. Phone #: ###-#### Internet Inspection Request from: Clay Morgan called, left correction notice, NEC 250.53(G) electrode shall have upper end flush with or below ground at service, 250.52(A)(1) metal u/g water pipe shall be used for grounding electrde within 5' of entering buiding, 250.86 metal enclosure shall be grounded (down bath),300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member-panel, kitchen header,210.52(A)(1) receptacles shall be spaced such that no point along floor line is over 6' from outlet-se bedroom, BCC shall change room count to 10 on permit
|