Permit Information
Permit NumberELE08-02902
StatusFinaled
Name SUBLIME ELECTRIC LLC
Site Address 1610 S JESSIE ST
Project Name 
Customer NumberDisaster k
ePlanReview 
Description
Electrical Permit - Repair: Rewire burnt home
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/21/200811/24/200811/24/2008APASS
DetailsMike Kinnear
Lock box code 1290, if you have any questions, please call Clay. Thank You. Phone #: ###-#### Internet Inspection Request from: Clay Morgan ok final
Rough-In Permanent Service11/3/200811/3/200811/3/2008PPASS
DetailsPat Lass
If you have any questions, please call Clay, Thank You. Phone #: ###-#### Internet Inspection Request from: Clay Morgan
P/S O/H R Ok
R/I Ok
Rough-In Permanent Service10/31/200811/3/200811/3/2008AFAIL
DetailsBob Reichert
House will be open, if you have any questions, please call Clay. Thank You. Phone #: ###-#### Internet Inspection Request from: Clay Morgan called, left correction notice, NEC 250.53(G) electrode shall have upper end flush with or below ground at service, 250.52(A)(1) metal u/g water pipe shall be used for grounding electrde within 5' of entering buiding, 250.86 metal enclosure shall be grounded (down bath),300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member-panel, kitchen header,210.52(A)(1) receptacles shall be spaced such that no point along floor line is over 6' from outlet-se bedroom, BCC shall change room count to 10 on permit