Final | 1/7/2009 | 1/7/2009 | 1/7/2009 | P | PASS |
Mike Kinnear
|
|
|
UL was under clear reflector, took apart and left open to view Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok final light fixtures are listed
|
Final | 1/6/2009 | 1/6/2009 | 1/6/2009 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson corrections except for fixtures made, called, contractor will call back when can show listing on fixtures
|
Final | 1/1/2009 | 1/2/2009 | 1/2/2009 | A | FAIL |
Jack Frank
|
|
|
Key is above door Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called corr. B. M. C. 4-05-33 light fixtures shall be labeled and listed 210.62 show window recepts shall be not more than 18" above window, 410.62(C)(1) if cord and plug connected fixture shall be located directory below outlet, 600.5 shall provide 20 amp dedicated sign circuit, 100.26(F)(1) shall remove low voltage conduit and wiring from below panel
|
Rough-In Permanent Service | 12/2/2008 | 12/2/2008 | 12/2/2008 | P | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok cover walls & hard lid ceilings only p/s u/g n ok (meter only) note t/w therrin regarding edison curcuits three pole brkers check at final
|
Conference | 11/7/2008 | 11/10/2008 | 11/10/2008 | P | DONE |
Bob Reichert
|
|
|
If possible around 2PM Phone #: ###-#### Internet Inspection Request from: Therrin Robertson went to jobsite, could not get contractor on phone till done, but tenant showed the equipment he wants to use. Contractor called and discussed putting gfci protection for the tanks and fixtures readily accesible, discussed not mounting ballasts to combustible framing with tenant.
|