Final | 3/9/2009 | 3/9/2009 | 3/9/2009 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok card signed
|
Final | 3/6/2009 | 3/6/2009 | 3/6/2009 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson called contractor, left correction notice,NEC 210.8(B)(5) receptacles installed within 6' of sink shall be gfci protected, 422.31(B) shall provide disconnects capable of being locked open for appliances, or in sight of units, 330.30(B) shall strap mc within 12" of box at contactor box, 110.22 shall label and identify panels
|
Permanent Service | 11/25/2008 | 11/26/2008 | 11/26/2008 | A | PASS |
Bob Reichert
|
|
|
p/s u/g n ok
|
Rough-In Permanent Service | 11/25/2008 | 11/26/2008 | 11/26/2008 | A | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/25/2008 at 12:50:46 PM.
|
Rough-In Permanent Service | 11/24/2008 | 11/25/2008 | 11/25/2008 | A | CANC |
Bob Reichert
|
|
|
just barely missed the 11:30 cut off time. If inspector schedule allows can be done this afternoon Mon the 24th Phone #: ###-#### Internet Inspection Request from: Tracy Robertson see ri, talked to contractor about 2 permits for service are required
|
Electrical Rough-In | 11/25/2008 | 11/25/2008 | 11/25/2008 | A | PASS |
Bob Reichert
|
|
|
just barely missed the 11:30 cut off time. If inspector schedule allows can be done this afternoon Mon the 24th Phone #: ###-#### Internet Inspection Request from: Tracy Robertson called, left message ,ric ok
|