Final | 2/11/2009 | 2/12/2009 | 2/12/2009 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 2/11/2009 at 4:31:00 PM. Contact: ###-####. ok card signed
|
Final | 2/10/2009 | 2/11/2009 | 2/11/2009 | P | PART |
Jack Frank
|
|
|
daniel - please call 1/2 hr prior Phone #: ###-#### t/o ok card signed needs to address low voltage supported on conduit 300.11
|
Final | 2/4/2009 | 2/4/2009 | 2/4/2009 | P | FAIL |
Jack Frank
|
|
|
daniel Note: also panel Phone #: ###-#### corr. posted met ele. contr. BCC 4-05-32, and 110.26(F)(1) remove exhaust fan from above main switch gear, BCC4-05-33, and 110.2&3, factory wired cabinets shall be labeled and listed, or ele. contr. can rewire to NEC, note when I told general contr he said that he it was a problem , and Portland inspector posted a correction for the same violation. 210.8 gfci other than dwelling 6ft of sinks and drinking fountain, 250.104, 250.66 bond hot and cold sized to T 250.66, strap MC re-loc 12" of boxes and terminations
|
Permanent Service | 2/4/2009 | 2/4/2009 | 2/4/2009 | P | CANC |
Jack Frank
|
|
|
daniel Note: also panel service Phone #: ###-#### no p/s required
|
Electrical Rough-In | 1/23/2009 | 1/23/2009 | 1/23/2009 | P | PART |
Jack Frank
|
|
|
Daniel Phone #: ###-#### rest rms office, supply rm, and corridors ceilings ok
|
Electrical Rough-In | 12/16/2008 | 12/17/2008 | 12/17/2008 | A | PART |
Jack Frank
|
|
|
daniel Phone #: ###-#### walls office and restrms
|