Temporary Service | 11/25/2008 | 11/25/2008 | 11/25/2008 | P | PASS |
Bob Reichert
|
|
|
Hi Bob, I have taken care of the red tag issues on the temp. pole. If you need anything else please call. Thx. Wayne Phone #: ###-#### Internet Inspection Request from: Wayne Craig corrections made, t/s o/h n ok, no esc this project
|
Temporary Service | 11/21/2008 | 11/24/2008 | 11/24/2008 | A | FAIL |
Bob Reichert
|
|
|
Hi Bob, The temp. power pole is located at the back of the property, if you have any questions please call. Thx. Wayne Phone #: ###-#### Internet Inspection Request from: Wayne Craig called left correction notice, NEC 250.24(A) gec shall connect to grounded service conductor, 250.53(G) upper end of electrode shall be flush with or below ground unless protected from physical damage, fee due, no esc this project
|
Final | 11/21/2008 | 11/24/2008 | 11/21/2008 | A | CANC |
Bob Reichert
|
|
|
Hi Bob,
I need an inspection on the temp. power pole. The temp. power pole is located in the back of the property, if you have any questions please call.
Thx. Wayne Phone #: ###-#### Internet Inspection Request from: Wayne Craig Inspection cancelled from web by: Wayne Craig
|