Final | 12/19/2008 | 12/19/2008 | 12/19/2008 | P | PASS |
Jack Frank
|
|
|
I will be unlocking the door this morning. Please call if there are any questions or concerns.
Thank You! And Happy Holidays! Phone #: ###-#### Internet Inspection Request from: Darryn Coburn ok
|
Electrical Rough-In | 11/24/2008 | 11/25/2008 | 11/25/2008 | A | PASS |
Bob Reichert
|
|
|
darrin Phone #: ###-#### corrections made, ric ok
|
Rough-In Permanent Service | 11/24/2008 | 11/24/2008 | 11/24/2008 | P | CANC |
Bob Reichert
|
|
|
darren Phone #: ###-#### wrong type request see p/s
|
Permanent Service | 11/24/2008 | 11/24/2008 | 11/24/2008 | P | PASS |
Bob Reichert
|
|
|
darren Phone #: ###-#### p/s u/g n ok
|
Electrical Rough-In | 11/24/2008 | 11/24/2008 | 11/24/2008 | P | FAIL |
Bob Reichert
|
|
|
darren Phone #: ###-#### called contractor, left correction notice,NEC 334.30 nm cable shall not be stapled on edge, and shall be stapled within 12" of panel, 210.52(H) hallway over 10' shall have receptacle outlet
|