Electrical Rough-In | 12/10/2008 | 12/10/2008 | 12/10/2008 | P | PASS |
Bob Reichert
|
|
|
ready for your inspection thanx joe Phone #: ###-#### Internet Inspection Request from: joe wheeler corections made, ric ok, no esc this project
|
Final | 12/10/2008 | 12/10/2008 | 12/10/2008 | P | PASS |
Bob Reichert
|
|
|
ready for your inspection thanx joe Phone #: ###-#### Internet Inspection Request from: joe wheeler ok to final, no esc this project
|
Electrical Rough-In | 12/8/2008 | 12/9/2008 | 12/9/2008 | A | FAIL |
Bob Reichert
|
|
|
if you can give me 30 min lead time i can be there to make sure trailer is open. thanks joe Phone #: ###-#### Internet Inspection Request from: joe wheeler called, left correction notice, NEC550.32(A) service disconnect shall be in sight and not more than 30' from exterior wall of mobile home, 408.4 circuit directory shall be clear and complete, Note: corrections shall be made within 2 working days, ok to cover u/g, no esc this project
|