Final | 8/10/2009 | 8/10/2009 | 8/10/2009 | P | PASS |
Jack Frank
|
|
|
please call me 1/2 hour before so i can get over there and that the GC can bring the sign off card over also. thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig ok card signed
|
Electrical Rough-In | 7/22/2009 | 7/22/2009 | 7/22/2009 | P | PASS |
Jack Frank
|
|
|
this is for cover on the atm canopy lights Phone #: ###-#### Internet Inspection Request from: Don Lustig
|
Electrical Rough-In | 6/29/2009 | 6/29/2009 | 6/29/2009 | P | PASS |
Jack Frank
|
|
|
underground light pole conduits in parking lot remodel Phone #: ###-#### Internet Inspection Request from: Don Lustigu/g for new parking lot ok
|
Final | 6/4/2009 | 6/4/2009 | 6/4/2009 | P | PART |
Jack Frank
|
|
|
this is for a temp final due to phasing of parking lot call me when heading to the job so i can walk thru thanks don ###-#### Phone #: ###-#### Internet Inspection Request from: Don Lustig corr posted 400.8(5) no cords allowed above ceiling, drive thur canopy, remove low voltage above main switch gear, 406.4(D) recepts in steel kick plates shall project pass the stel plate 0.015 t/o ok card signed
|
Electrical Rough-In | 4/29/2009 | 4/29/2009 | 4/29/2009 | A | PASS |
Bob Reichert
|
|
|
this is to relook at the ceiling for cover on the pendent lights Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to cover rest of ceiling for pendant lights anop
|
Electrical Rough-In | 4/28/2009 | 4/28/2009 | 4/28/2009 | A | PART |
Bob Reichert
|
|
|
Ceiling cover on suspended ceilings Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to cover ceilings anop, called contractor provide installation instructions for cable hung fixtures
|
Permanent Service | 4/17/2009 | 4/17/2009 | 4/17/2009 | P | PASS |
Bob Reichert
|
|
|
service inspection ready noon and beyound i will call when ready so the power can turn back on thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig called contractor, p/s u/g n ok (sticker on meter at transformer)
|
Electrical Rough-In | 4/16/2009 | 4/16/2009 | 4/16/2009 | P | PART |
Bob Reichert
|
|
|
This is for partial ceiling cover high ceilings at entry. there are no electrical in this area. Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to cover high ceilings only, no wiring above tiles, anop
|
Electrical Rough-In | 4/2/2009 | 4/2/2009 | 4/2/2009 | P | PASS |
Bob Reichert
|
|
|
This is for underground cover south side of building i will be ready around 11 or so i will call you when close thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to cover u/g south and west side
|
Electrical Rough-In | 3/18/2009 | 3/18/2009 | 3/18/2009 | A | PASS |
Bob Reichert
|
|
|
OK this is the last RI inspection needed for hard lid Ceiling cover electrical room and interior soffits Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to cover hard ceiling in electrical room and soffits for interior
|
Electrical Rough-In | 3/17/2009 | 3/17/2009 | 3/17/2009 | A | PASS |
Bob Reichert
|
|
|
This is for cover of Drive Thru ceilings outside. it is ready so as soon as you can swing by that would be great. Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig drive-thru ceiling only ok to cover anop
|
Electrical Rough-In | 3/16/2009 | 3/16/2009 | 3/16/2009 | A | PASS |
Bob Reichert
|
|
|
This for interior wall cover Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to cover interior walls only anop
|
Electrical Rough-In | 3/11/2009 | 3/11/2009 | 3/11/2009 | P | PASS |
Bob Reichert
|
|
|
Hello this is for the upper outside soffits for cover i will be on site Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to cover upper level soffit lights anop
|
Electrical Rough-In | 3/5/2009 | 3/5/2009 | 3/5/2009 | P | PASS |
Bob Reichert
|
|
|
This is for all exterior walls and soffits cover Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to cover exterior walls and lower soffits only anop
|
Conference | 2/26/2009 | 2/26/2009 | 2/26/2009 | P | DONE |
Bob Reichert
|
|
|
met with vendor, owners, contractors to discuss office furnishings listings and installation requirements
|
Electrical Rough-In | 1/23/2009 | 1/23/2009 | 1/23/2009 | P | PASS |
Bob Reichert
|
|
|
Hello Bob digging did not go as fast as planned i will be ready around 11 i will call you if sooner so you can fit in when available. Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig met contractor, ok to cover drive-thru area only anop
|
Electrical Rough-In | 1/22/2009 | 1/22/2009 | 1/22/2009 | P | FAIL |
Bob Reichert
|
|
|
drive thur underground piping cover inspection Phone #: ###-#### Internet Inspection Request from: Don Lustig met contractor, gave correction notice,NEC 300.5 raceways shall be 2' below top of concrete
|
Electrical Rough-In | 12/9/2008 | 12/9/2008 | 12/9/2008 | P | PASS |
Mike Kinnear
|
|
|
Ufer ground needs looked at i will get it in this morning they will pour on wednesday Phone #: ###-#### Internet Inspection Request from: Don Lustig ok cover concrete incased electrode
|