Permit Information
Permit NumberELE08-03209
StatusFinaled
Name BLACKHAM ELECTRIC
Site Address 3303 W HAMILTON ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/17/20093/17/20093/17/2009APASS
DetailsBob Reichert
call for entry to home Phone #: ###-#### Internet Inspection Request from: Brandon Blackham met contractor, ok to final, could not add esc inspection
Rough-In Permanent Service12/14/200812/15/200812/15/2008APASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham corrections made, ric ok, p/s o/h rec ok
Rough-In Permanent Service12/11/200812/11/200812/11/2008PFAIL
DetailsBob Reichert
brandon Phone #: ###-#### called, left correction notice, NEC 300.14 shall have at least 6" free conductor length at outlet boxes, 210.52(A) shall provide receptacle in south kitchen wall, 110.12(B) shall not use broken box in bathroom ( clamp for nm broken out),110.11 shall not have re-bar exposed to elements for gec, 250.94 shall provide intersystem bonding bar, BCC house shall be brought up to code, Note: corrections shall be made within 2 working days