Final | 3/17/2009 | 3/17/2009 | 3/17/2009 | A | PASS |
Bob Reichert
|
|
|
call for entry to home Phone #: ###-#### Internet Inspection Request from: Brandon Blackham met contractor, ok to final, could not add esc inspection
|
Rough-In Permanent Service | 12/14/2008 | 12/15/2008 | 12/15/2008 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham corrections made, ric ok, p/s o/h rec ok
|
Rough-In Permanent Service | 12/11/2008 | 12/11/2008 | 12/11/2008 | P | FAIL |
Bob Reichert
|
|
|
brandon Phone #: ###-#### called, left correction notice, NEC 300.14 shall have at least 6" free conductor length at outlet boxes, 210.52(A) shall provide receptacle in south kitchen wall, 110.12(B) shall not use broken box in bathroom ( clamp for nm broken out),110.11 shall not have re-bar exposed to elements for gec, 250.94 shall provide intersystem bonding bar, BCC house shall be brought up to code, Note: corrections shall be made within 2 working days
|