Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberELE08-03254
StatusFinaled
Name MOUNTAIN POWER ELECT
Site Address 234 S WHISPERWOOD
Project NameMEP GROUP LLC
Customer Number09-001
ePlanReview 
Description
Electrical Permit TI ONLY- New: Electrical wiring for new MEP Group LLC Building. Includes Light Fixtures, Switchgear, Power, HVAC and Fire Alarm installation.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/29/20095/29/20095/29/2009PPASS
DetailsJack Frank
Darren Phone #: ###-####
Final5/27/20095/28/20095/28/2009APART
DetailsJack Frank
Darren Phone #: ###-#### T/O ok card signed
Final5/27/20095/27/20095/27/2009PCANC
DetailsJack Frank
Darren Phone #: ###-#### still needs ELE permit for core and shell and shall be attached to core&shell BLD,,,,, 370 told them that on 03-09-09
Final5/21/20095/22/20095/22/2009ACANC
DetailsJack Frank
darren- part Phone #: ###-#### see added r/i ok to bring office furiture in
Electrical Rough-In5/22/20095/22/20095/22/2009APASS
DetailsJack Frank
darren- part Phone #: ###-#### all ceilings ok
Electrical Rough-In5/19/20095/19/20095/19/2009PPART
DetailsJack Frank
darren - late afternoon please Phone #: ###-#### ceilings anop
Electrical Rough-In5/14/20095/15/20095/15/2009ACANC
DetailsBob Reichert
Darren Phone #: ###-#### see conference, no esc this project
Conference5/15/20095/15/20095/15/2009ADONE
DetailsBob Reichert
Darren Phone #: ###-#### met electrician, they wanted to do partial ceilings because they have fan coils up, but no lighting. Told them no borders and that fixtures had to be installed for ceiling inspection, no esc this project
Rough-In Permanent Service5/4/20095/5/20095/5/2009APASS
DetailsBob Reichert
Daren Phone #: ###-#### ri ok, conduit concrete encased, p/s u/g n ok, sticker on meter at transformer, no esc this project
Rough-In Permanent Service4/27/20094/28/20094/28/2009ACANC
DetailsBob Reichert
darrin Phone #: ###-#### see conference, no esc this project
Conference4/28/20094/28/20094/28/2009ADONE
DetailsBob Reichert
darrin Phone #: ###-#### met contractor, had him check available fault current available from ipco, he will change 2 breakers, reviewed 230.6 for concrete encasemnt for service conduits, they shall be concrete encased or provide a disconnect on outside of building, no esc this project
Electrical Rough-In4/17/20094/17/20094/17/2009PPASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 4/17/2009 at 8:53:52 AM. Contact: ###-####. ok to cover u/g for site work, no esc this project
Electrical Rough-In4/14/20094/14/20094/14/2009PCANC
DetailsBob Reichert
Darren- Late PM if possible Phone #: ###-#### called , they won't be ready, will call for later inspection, no esc this project
Conference4/9/20094/10/20094/10/2009ADONE
DetailsBob Reichert
darren Phone #: ###-#### talked about clearances for fire alarm panel, they need to turn faucet another direction, no esc this project
Electrical Rough-In3/23/20093/23/20093/23/2009PPASS
DetailsBob Reichert
Darren Phone #: ###-#### upper walls and hard lid ok to cover anop
Electrical Rough-In3/16/20093/16/20093/16/2009PPART
DetailsBob Reichert
Darren Phone #: ###-#### 1st foor interior walls ,hard lids, and soffits only ok to cover anop, no esc this project
Electrical Rough-In3/11/20093/12/20093/12/2009PPASS
DetailsBob Reichert
Darren Phone #: ###-#### ok to cover outer office walls, hard lids in baths, under trusses anop, no esc this project
Electrical Rough-In3/6/20093/9/20093/9/2009APASS
DetailsBob Reichert
darren Phone #: ###-#### ok to cover exterior soffits and perimeter walls only, told contractor this is shell and core only permit
Conference1/26/20091/26/20091/26/2009PDONE
DetailsBob Reichert
darin Note: just a telephone will be fine Phone #: ###-#### talked about conduit in crawl space for commercial building and also mc cable, said conduit supported on grade with supports is ok
Electrical Rough-In12/19/200812/22/200812/22/2008APASS
DetailsBob Reichert
darin Note: ufier Phone #: ###-#### Note: first in Morning pour concrete at 10:00 ok to pour concrete encased electrode