Final | 4/20/2009 | 4/21/2009 | 4/21/2009 | A | PASS |
Pat Lass
|
|
|
Joe Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt
|
Electrical Rough-In | 4/17/2009 | 4/20/2009 | 4/20/2009 | A | PASS |
Jack Frank
|
|
|
O.K. to cover PVC for plug & light on gazebo. West side of house. Will have concrete over PVC. Joe Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt ok
|
Electrical Rough-In | 1/26/2009 | 1/27/2009 | 1/27/2009 | A | PASS |
Pat Lass
|
|
|
Meet with Joe at 8:30 am. Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt
|
Rough-In Permanent Service | 1/22/2009 | 1/23/2009 | 1/23/2009 | A | PART |
Pat Lass
|
|
|
joe Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt loose crimps still will check later ok to cover R/I P/S O/H N Ok
|
Rough-In Permanent Service | 1/21/2009 | 1/22/2009 | 1/22/2009 | A | FAIL |
Jack Frank
|
|
|
Joe Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt corr for high and low voltage wiring, called, needs connectors at outside pancake boxes where 1/2" ko is used, also connectors or bushings ay low voltage cabinet 110.14 splices loose wrong tool used for grd wire crimp sleeves 334.30 and 314.17(C) shall staple romex within 8", or 12" of boxes, 300.4 nail plaetes, note u/g too bomb shelter covered before inspection, outside back recept not wired, provide access at electrode connection
|