Final | 1/13/2009 | 1/14/2009 | 1/14/2009 | A | PASS |
Bob Reichert
|
|
|
butch Phone #: ###-#### corrections made, ok to final, no esc this project
|
Permanent Service | 1/12/2009 | 1/12/2009 | 1/12/2009 | P | PASS |
Bob Reichert
|
|
|
butch Phone #: ###-#### corrections to be done by final,NEC 110.26(F)(2) no foreign piping systems shall be installed in dedicated space (meter). 110.26(A) shall provide work spce in front of panel, 250.140 range and dryer shall have frames connected to equipment grounding conductor, 312.5 all conductors entering enclosure shall have abrasion protection, p/s u/g rec ok, no esc this project
|