Permanent Service | 1/27/2009 | 1/28/2009 | 1/28/2009 | P | PASS |
Mike Kinnear
|
|
|
Pat Phone #: ###-#### p/s o/h reconnect ok shop only
|
Final | 1/28/2009 | 1/28/2009 | 1/28/2009 | P | PASS |
Mike Kinnear
|
|
|
Pat Phone #: ###-#### ok final note no esc permit in project
|
Permanent Service | 1/22/2009 | 1/23/2009 | 1/23/2009 | P | CANC |
Bob Reichert
|
|
|
This is in the shop on the back side of the property. Call Nate for entrance. if it passes the permanent please final Phone #: ###-#### see conference
|
Conference | 1/23/2009 | 1/23/2009 | 1/23/2009 | P | DONE |
Bob Reichert
|
|
|
This is in the shop on the back side of the property. Call Nate for entrance. if it passes the permanent please final Phone #: ###-#### called contractor, told him that he needs to verify service conductors are sun-light resistant, shall use plastic bushing for abrasion protection for gec, riser clamps shall be repaired,abandon existing ground or provide chokes, owner asked about re-connect power to house, told that it must be brought up to code and needs a permit - power has been off for 2 years or so, no esc this project
|
Final | 1/22/2009 | 1/23/2009 | 1/23/2009 | P | CANC |
Mike Kinnear
|
|
|
This is in the shop on the back side of the property. Call Nate for entrance. Phone #: ###-#### Internet Inspection Request from: Todd Sellman
|