Final | 3/24/2009 | 3/24/2009 | 3/24/2009 | A | PASS |
Bob Reichert
|
|
|
I wont be on site but check it out and let me know if you have any questions Thanks Don Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to final, signed occupancy card
|
Electrical Rough-In | 3/12/2009 | 3/12/2009 | 3/12/2009 | P | PASS |
Bob Reichert
|
|
|
Don Phone #: ###-#### corrections made, ok to cover ceiling
|
Electrical Rough-In | 3/11/2009 | 3/11/2009 | 3/11/2009 | A | FAIL |
Bob Reichert
|
|
|
Hello this is for ceiling grid cover call me with any questions Phone #: ###-#### Internet Inspection Request from: Don Lustig called contractor, left correction notice, NEC 300.11(A) independent support wires shall be secured at both ends (low and high voltage), 300.11(B) raceways shall not support lv cables, BCC shall close boxes above ceiling, shall obtain electrical permit for hvac work
|
Electrical Rough-In | 2/9/2009 | 2/10/2009 | 2/10/2009 | A | PART |
Jack Frank
|
|
|
Rough in cover for the restroom Matt should be on site the heating contractor is running power for the rtu''s they need a separate permit. Phone #: ###-#### Internet Inspection Request from: Don Lustig walls and ceilings rest rms ok
|
Electrical Rough-In | 2/6/2009 | 2/6/2009 | 2/6/2009 | P | PASS |
Bob Reichert
|
|
|
Wall cover call Matt on site for walk thru at ###-#### Phone #: ###-#### Internet Inspection Request from: Don Lustig walls only ok to cover
|