Final | 6/27/2011 | 6/27/2011 | 6/27/2011 | P | PASS |
Daryl DeGrange
|
|
|
Kathy-please call at least 30 mins in advance Phone #: ###-#### final ok
|
Final | 6/22/2011 | 6/23/2011 | 6/23/2011 | A | FAIL |
Daryl DeGrange
|
|
|
kathy Phone #: ###-#### - please call 1/2 hr prior NEC 408.7 unsued openings in panel shall be closed using identified closures. A/C unit requires proper ampage breaker
|
ELE-Aging Inspection | 4/20/2011 | 4/20/2011 | 4/20/2011 | | DONE |
Daryl DeGrange
|
|
|
still under construction, home owner thought she (Kathy) would be ready for final by 4/25/11
|
ELE-Aging Inspection | 2/18/2011 | 2/18/2011 | 2/23/2011 | | DONE |
Daryl DeGrange
|
|
|
no activity
|
ELE-Aging Inspection | 11/29/2010 | 11/29/2010 | 12/2/2010 | | DONE |
Daryl DeGrange
|
|
|
suc called 12/02/10 home ower hopes to be completed by 12/31/10
|
ELE-Aging Inspection | 9/28/2010 | 9/28/2010 | 9/29/2010 | | DONE |
Bob Reichert
|
|
|
no activity, suc
|
Electrical Rough-In | 3/18/2009 | 3/18/2009 | 3/18/2009 | P | PASS |
Mike Kinnear
|
|
|
Kathy ###-####//please call 30 min prior to meet ok cover ri note no esc permit in project
|
Electrical Rough-In | 3/18/2009 | 3/18/2009 | 3/18/2009 | P | FAIL |
Jack Frank
|
|
|
Kathy ###-####//please call 30 min prior to meet corrections not made owner wanted to argue I left job
|
Electrical Rough-In | 3/16/2009 | 3/17/2009 | 3/17/2009 | P | FAIL |
Pat Lass
|
|
|
Kathy ###-####//please call 20 min. prior to meet box fill, screws not permited inside nm boxes, boxes over filled, parallel protection of romex, and free conductor.
|
Conference | 2/27/2009 | 3/2/2009 | 3/2/2009 | P | PART |
Pat Lass
|
|
|
Kathy ###-#### talked about general requirements
|