Permit Information
Permit NumberELE09-00346
StatusFinaled
Name ENERGIZED ELECTRIC
Site Address 2207 W OVERLAND RD
Project NameSAMMY'S
Customer Number 
ePlanReview 
Description
install exit signs and power for fire alarm panel per cert of value $ 800.00 /// DLD
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled  5/27/2011 DONE
collection fees paid - changed status back to finaled
Final4/1/20094/1/20094/1/2009PPASS
DetailsJack Frank
ok card signed
Rough-In Permanent Service3/26/20093/30/20093/30/2009ACANC
DetailsJim Schmer
contr. Donny ###-#### 10:00 AM cancel bob went friday and owner said enterprise is going to make corrections. talked to enterprise, clint (?), he said that they would do it and permit it. JMS
Final3/27/20093/27/20093/27/2009PPART
DetailsBob Reichert
Tony-Temp Occupancy Phone #: ###-#### ok for temp occupancy, signed card, items on correction taken care except grounding and bonding at service. Added note stating that corrections shall be completed by 4-1-09 or further action will be taken such as removal of power. Copy of correction left with owner.
Final3/26/20093/26/20093/26/2009PFAIL
DetailsJack Frank
Donny Phone #: ###-#### called all violations not corrected, remove all extension cords and install recepts on ceiling for lights, as correcton posted states, services shall be grounded and bonded to meet art. 250 2008 NEC needs bond screws, or straps at service panels, shall use myers hubs listed for grounding and bonding meeting (UL) 939K, or install bonding wedges or bond bushing on existing non listed myers hubs
Final3/18/20093/19/20093/19/2009PFAIL
DetailsJack Frank
this is just a few exit lights and some minor code violation needed fixed. also there are two panels where the main switches are not grouped nothing has been done to that I know this is a violation but the owners dont believe things we tell them. just letting you know we are not trying to pull the wool over your eyes or that we are not aware of the nec. thanks don simpson Phone #: ###-#### Internet Inspection Request from: DONNY SIMPSON corr met electrician, shall provide labels for more than 1 service to bld 230.2 (D&E), BCC no violations retained, all grounding and bonding for service shall meet 2008 article 250, 400.7&8 shall remove all cord used as fixed wiring for djay lighting, 410.62(C) electric discharge fixtures shall use recept and cord cap, with recept above fixture, support jbox above p/s seal all unused breaker KOs