Final | 4/3/2009 | 4/3/2009 | 4/3/2009 | P | PASS |
Pat Lass
|
|
|
roger Phone #: ###-#### this is for the service only
|
Permanent Service | 3/27/2009 | 3/27/2009 | 3/27/2009 | P | PASS |
Pat Lass
|
|
|
late pm please call when on way out//Roger Goodman ###-#### P/S O/H R Ok to transfer power
|
Permanent Service | 3/18/2009 | 3/19/2009 | 3/19/2009 | A | CANC |
Pat Lass
|
|
|
Roger Phone #: ###-#### still no bld permit
|
Permanent Service | 3/13/2009 | 3/16/2009 | 3/16/2009 | P | FAIL |
Jack Frank
|
|
|
Roger ###-#### corr. met contr note owner needs bld for occupancy with ele attached, 250.52 (A)(1) &104(A)(1) GEC within 5 ft , and bond hot and cold, 310.16 needs 3/0 cu. or 250 kc mil al for service also sun/res, 110.26(F)(1) clearence for p/s and subpanel, 230.54(B)(4) clearence from grade to p/s drop at lowest point shall be 18FT 230.24(C) srevice drop shall not be above weatherhead exception does not apply BCC and 410.62(C) if cord used for fixtures needs factory canopy or recept and cord cap,
|