Final | 5/14/2009 | 5/15/2009 | 5/15/2009 | A | PASS |
Bob Reichert
|
|
|
Please provide electrical final for adding vacuums. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean corrections made, ok to final, no esc this project
|
Final | 5/13/2009 | 5/14/2009 | 5/14/2009 | A | FAIL |
Jack Frank
|
|
|
Please provide final inspection for the three newly added vacuums. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean called corr. 250.148, & 250.122 shall splice all equip grds together in outside j box and use #10 grd pigtail to grd box
|
Electrical Rough-In | 5/1/2009 | 5/1/2009 | 5/1/2009 | P | PASS |
Bob Reichert
|
|
|
Provide underground inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean ok to cover u/g only, no esc this project
|