Final | 7/13/2009 | 7/14/2009 | 7/14/2009 | A | PASS |
Bob Reichert
|
|
|
If pass, please sign building permit left on "table" in construction area. Thank you Phone #: ###-#### Internet Inspection Request from: Scott Kraemer called, ok to final, signed card, no esc this project
|
Electrical Rough-In | 7/6/2009 | 7/7/2009 | 7/7/2009 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Scott Kraemer corrections made, ric ok, no esc this project
|
Electrical Rough-In | 7/2/2009 | 7/6/2009 | 7/6/2009 | A | FAIL |
Bob Reichert
|
|
|
please call if there any problems or questions. I will be in the area. Phone #: ###-#### Internet Inspection Request from: Scott Kraemer called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member or use steel plates to protect cable, 110.12(B) there shall be no broken or damaged parts-cable, 314.23(E) boxes shall not be supported by racways, no esc this project
|