Final | 7/10/2009 | 7/10/2009 | 7/10/2009 | P | PASS |
Bob Reichert
|
|
|
Ron Phone #: ###-#### corrections made, ok to final, will get new permit for rest of work no card to sign
|
Final | 6/16/2009 | 6/17/2009 | 6/17/2009 | A | NR |
Jack Frank
|
|
|
Ron Phone #: ###-#### called needs show window recepts, strap emt counter remove sq d bearkers from ITE panel install jboxes conduits south side outdoor wall
|
Electrical Rough-In | 5/19/2009 | 5/20/2009 | 5/20/2009 | A | PASS |
Jack Frank
|
|
|
Clide Phone #: ###-#### r/i ok walls and ceilings
|
Electrical Rough-In | 5/14/2009 | 5/14/2009 | 5/14/2009 | P | FAIL |
Jack Frank
|
|
|
ron beckman Phone #: ###-#### corr. met contr. 300.4(D) parallel protection for flex, 348.24&30 flex bent too tight for radius, strap 12" of boxes, 358.30 strap emt within 3ft boxes, 230.70(A)(2) and BCC 04-05-31(A) service and subpanels not allowed in bathrooms
|