Final | 8/11/2009 | 8/11/2009 | 8/11/2009 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/11/2009 at 5:57:06 AM. Contact: ###-####. ok to final, met contractor, told to check availabe fault current with ipco
|
Rough-In Permanent Service | 5/27/2009 | 5/27/2009 | 5/27/2009 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 5/27/2009 at 6:16:34 AM. Contact: ###-####. r/i p/s u/g new ok
|
Rough-In Permanent Service | 5/22/2009 | 5/26/2009 | 5/26/2009 | A | FAIL |
Jack Frank
|
|
|
Dino Phone #: ###-#### called corr. 210.52(A&C) needs receps for wall space fixed panel patio door and countertop in din rm 334.23 protect all cables 6ft of attic access, 314.17&362.6 bushings for cables, and conn for ENT at low voltage cabinet
|