Final | 7/6/2009 | 7/6/2009 | 7/6/2009 | A | PASS |
Doug A Poedy
|
|
|
Scheduled by a contractor via Hello! on 7/6/2009 at 6:43:35 AM. Contact: ###-####. Ok final, no esc permit.
|
Electrical Rough-In | 6/10/2009 | 6/11/2009 | 6/11/2009 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/10/2009 at 3:23:37 PM. Contact: ###-####. corrections made, ric ok, no esc this project
|
Electrical Rough-In | 6/10/2009 | 6/10/2009 | 6/10/2009 | P | FAIL |
Bob Reichert
|
|
|
tom Phone #: ###-#### called, left message, left correction notice, NEC 210.52(C)(1) shall install receptacle in countertop right of sink, 210.52(A) shall provide receptacle in wall right of entry door, 314.22(B)(1) there shall be no screws in box to support to framing members, 334.30 shall secure nm cable within 8" of box, 300.4(A) shall provide nailplates for bored holes if edge of hole is less than 1 1/4" from edge of framing member, no esc this project
|