Permanent Service | 6/29/2009 | 6/30/2009 | 6/30/2009 | A | PASS |
Jack Frank
|
|
|
neil Phone #: ###-#### p/s o/h rec. ok
|
Final | 6/30/2009 | 6/30/2009 | 6/30/2009 | A | PASS |
Jack Frank
|
|
|
neil Phone #: ###-#### ok
|
Final | 6/25/2009 | 6/26/2009 | 6/26/2009 | A | PASS |
Jack Frank
|
|
|
ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten called contr needs to seal KO trailer panel. and at p/s terminate GEC to neutral bus ok
|
Rough-In Permanent Service | 6/15/2009 | 6/17/2009 | 6/17/2009 | A | FAIL |
Bob Reichert
|
|
|
space #17 service is ready, it is unoccupied, help yorself Phone #: ###-#### Internet Inspection Request from: gary batten called,left message, left correction notice, NEC 352.39(A) shall securely support pvc within 3' of termination, 342.30(A) shall securely support imc within 3' of termination, 312.5 all conductors entering enclosure shall have abrasion protection, 110.12(A) unused openings shall be closed in electrical equipment, 334.15(B) nm cable shall be protected from physical damage, 408.4 shall provide circuit directory
|