Final | 2/11/2010 | 2/12/2010 | 2/12/2010 | A | PASS |
Doug A Poedy
|
|
|
Please contact Clayton Pennington prior to inspection. Inspection requested from web by: Spencer Mclean Phone #: ###-####
|
DOC - Permit Finaled | 2/12/2010 | 2/12/2010 | 2/12/2010 | P | PASS |
Doug A Poedy
|
|
|
|
Final | 1/27/2010 | 1/27/2010 | 1/27/2010 | P | PART |
Jack Frank
|
|
|
This is a final for the center and East wings of the building. Please contact Nick Larson prior to inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean ok
|
Final | 1/25/2010 | 1/26/2010 | 1/26/2010 | A | PART |
Jack Frank
|
|
|
This is a final for the west wing of the spring creek project. contact Nick Larson prior to inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean
|
Permanent Service | 12/22/2009 | 12/22/2009 | 12/22/2009 | P | PASS |
Jack Frank
|
|
|
Please provide electrical service inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean p/s u/g new ok
|
Permanent Service | 12/21/2009 | 12/21/2009 | 12/21/2009 | P | NR |
Jack Frank
|
|
|
Please provide service inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean called needs to grd or bond eater systems, also 200.2(B) GEC shall terminate at neutral bus
|
Electrical Rough-In | 11/25/2009 | 11/25/2009 | 11/25/2009 | P | PASS |
Doug A Poedy
|
|
|
Please provide a rough-in inspection on the library ceiling. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean Should complete entire building for cover.
|
Electrical Rough-In | 11/19/2009 | 11/20/2009 | 11/20/2009 | A | PASS |
Jack Frank
|
|
|
Please provide electrical rough-in inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean east wing , center, front area, walls hard ceilings
|
Final | 11/16/2009 | 11/17/2009 | 11/17/2009 | P | CANC |
Jack Frank
|
|
|
Please provide rough-in inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean see added r/i
|
Electrical Rough-In | 11/17/2009 | 11/17/2009 | 11/17/2009 | P | NR |
Jack Frank
|
|
|
Please provide rough-in inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean checked out work needs to correct box fill MC in plastic boxes, remove drain and sprinkler from above panels
|
Electrical Rough-In | 10/30/2009 | 11/2/2009 | 11/2/2009 | A | PART |
Bob Reichert
|
|
|
RI inspection for the east wing Phone #: ###-#### Internet Inspection Request from: Spencer Mclean ok to cover walls and ceilings anop- west 1/2 only, not east
|
Electrical Rough-In | 10/21/2009 | 10/22/2009 | 10/22/2009 | A | PASS |
Bob Reichert
|
|
|
Please provide soffit electrical cover inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean soffits only for outside perimeter ok to cover, told contractor to get set of prints to mark and do partial ri for sections of interiors, and if any cover before inspection, will have to take down what hides electrical, left sticker on front window
|
ELE-Aging Inspection | 9/11/2009 | 9/11/2009 | 9/11/2009 | | PART |
Jack Frank
|
|
|
wsuc
|
Electrical Rough-In | 6/30/2009 | 6/30/2009 | 6/30/2009 | P | PASS |
Jack Frank
|
|
|
Please provide uffer inspection on S.W. corner. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean ok
|
Electrical Rough-In | 6/18/2009 | 6/18/2009 | 6/18/2009 | P | PASS |
Jack Frank
|
|
|
Please provide uffer ground inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean electrode ok
|