Final | 8/17/2009 | 8/18/2009 | 8/18/2009 | A | PASS |
Jack Frank
|
|
|
Please call for access code-- Phone #: ###-#### Internet Inspection Request from: Rhonda Yoast ok
|
Electrical Rough-In | 6/23/2009 | 6/24/2009 | 6/24/2009 | A | PASS |
Bob Reichert
|
|
|
The corrections have been made. Phone #: ###-#### Internet Inspection Request from: Rhonda Yoast corrections made, no approved plans on job, ric ok
|
Permanent Service | 6/24/2009 | 6/24/2009 | 6/24/2009 | A | PASS |
Bob Reichert
|
|
|
The corrections have been made. Phone #: ###-#### Internet Inspection Request from: Rhonda Yoast p/s u/g n ok
|
Electrical Rough-In | 6/22/2009 | 6/23/2009 | 6/23/2009 | A | FAIL |
Jack Frank
|
|
|
Thank you. Phone #: ###-#### Internet Inspection Request from: Rhonda Yoast corr called 210.52(B) shall remove switch and light from SABC formal din rm, note 410.2 definition of closet storage space , and location of fixtures, 110.3(B) gas rangr recept on exhaust/micro wave circuit do manufacture's instructions allow it?312.5 bushings where low voltage enters cabinet, B C C shall provide city approved plans at job site and request p/s inspection not just r/i
|