Final | 11/18/2009 | 11/18/2009 | 11/18/2009 | P | PASS |
Bob Reichert
|
|
|
Contact: Mike Ennis Phone #: ###-#### Internet Inspection Request from: Melissa Kaae ok to final, signed structural card, no esc this project
|
Electrical Rough-In | 9/17/2009 | 9/17/2009 | 9/17/2009 | P | PASS |
Jack Frank
|
|
|
Contact: Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Melissa Kaae ceiling ok
|
Electrical Rough-In | 9/14/2009 | 9/14/2009 | 9/14/2009 | P | FAIL |
Bob Reichert
|
|
|
Contact: Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Melissa Kaae called left correction notice, NEC 348.42 shall not use angle connector in concealed ceiling, 348.30(A) fmc shall be securely fastened within12" of box and every 4 1/2', BCC all make-up shall be done, no esc this project
|
Conference | 7/16/2009 | 7/16/2009 | 7/16/2009 | A | DONE |
Bob Reichert
|
|
|
Please contact John Campbell for a conference. Phone #: ###-#### Internet Inspection Request from: Sarah Bastian talked about services and locations for waiting areas for shuttle people, no esc this project
|