Temporary Service | 7/12/2009 | 7/13/2009 | 7/13/2009 | A | PASS |
Bob Reichert
|
|
|
contact: Bob Schroder Phone #: ###-#### Internet Inspection Request from: Julie Schroder corrections made, t/s u/g n ok, no esc this project
|
Temporary Service | 7/9/2009 | 7/10/2009 | 7/10/2009 | A | FAIL |
Bob Reichert
|
|
|
contact: Bob Schroder Phone #: ###-#### Internet Inspection Request from: Julie Schroder called, left correction notice, NEC 406.8(B) 15 and 20a receptacles shall be listed weather resistant type, 250.24(A) grounding electrode conductor shall be connected to grounded service conductor, no esc this project
|
Temporary Service | 7/7/2009 | 7/7/2009 | 7/7/2009 | P | CANC |
Doug A Poedy
|
|
|
contact: Bob Schroder Phone #: ###-#### Internet Inspection Request from: Julie Schroder
|