Final | 8/13/2009 | 8/14/2009 | 8/14/2009 | A | PASS |
Bob Reichert
|
|
|
ron Phone #: ###-#### corrections made, ok to final
|
Final | 8/11/2009 | 8/12/2009 | 8/12/2009 | A | FAIL |
Bob Reichert
|
|
|
ron Phone #: ###-#### called, left correction notice,NEC 406.8(B) all receptacles shall be listed weather resistant type, 314.23(A) receptacle enclosure shall be rigidly and securely mounted, 358.42 emt couplings shall be made up tight and comply with 314.5, no esc this project
|
Electrical Rough-In | 7/13/2009 | 7/13/2009 | 7/13/2009 | P | PASS |
Bob Reichert
|
|
|
Ron Phone #: ###-#### ric ok
|