Final | 8/25/2009 | 8/26/2009 | 8/26/2009 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/25/2009 at 3:38:40 PM. Contact: ###-####. ok to final
|
Electrical Rough-In | 7/21/2009 | 7/21/2009 | 7/21/2009 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/21/2009 at 12:30:24 AM. Contact: ###-####. corrections made, ric ok
|
Rough-In Permanent Service | 7/20/2009 | 7/20/2009 | 7/20/2009 | P | CANC |
Bob Reichert
|
|
|
Tom Phone #: ###-#### see ri and p/s
|
Electrical Rough-In | 7/20/2009 | 7/20/2009 | 7/20/2009 | P | FAIL |
Bob Reichert
|
|
|
Tom Phone #: ###-#### called, left correction notice, NEC 210.70(A)(2) shall provide lighting outlets for exterior entrances front and rear and also garage man-door, 210.52(A) shall provide receptacle in 2' walls in kitchen and upper bedroom, 250.148(C) shall provide ground screw and grounding in metal boxes
|
Permanent Service | 7/20/2009 | 7/20/2009 | 7/20/2009 | P | PASS |
Bob Reichert
|
|
|
Tom Phone #: ###-#### p/s u/g n ok
|