Final | 8/17/2009 | 8/18/2009 | 8/18/2009 | A | PASS |
Bob Reichert
|
|
|
nathan Phone #: ###-#### corrections made, ok to final, signed occupancy card
|
Final | 8/12/2009 | 8/12/2009 | 8/12/2009 | P | PART |
Bob Reichert
|
|
|
Donny Phone #: ###-#### most corrections made, signed t/o card, will call back when equipment comes in, no esc this project
|
Final | 8/10/2009 | 8/10/2009 | 8/10/2009 | P | NR |
Jack Frank
|
|
|
Donny Phone #: ###-#### need eguip on site, also needs manufacture's listed breakers, notewhen breakers are mreplaced t/o can be given, but owner will need listed equipment, or get setup for field evaluation talked with contr
|
Final | 8/6/2009 | 8/7/2009 | 8/7/2009 | A | FAIL |
Jack Frank
|
|
|
corr called 110.2 and BMC 4-05-33 panini grill and autogyros not labeled or listed, 110.3(B) use only manufacture's approved breakers, 250.104 bond hot and cold water pipes
|
Final | 8/6/2009 | 8/6/2009 | 8/6/2009 | P | CANC |
Jack Frank
|
|
|
As late as possible please--Robert Phone #: ###-#### contr called
|
Final | 8/6/2009 | 8/6/2009 | 8/6/2009 | A | CANC |
Jack Frank
|
|
|
|
Electrical Rough-In | 7/27/2009 | 7/27/2009 | 7/27/2009 | P | PASS |
Jack Frank
|
|
|
robert Phone #: ###-#### walls ok
|
Electrical Rough-In | 7/23/2009 | 7/23/2009 | 7/23/2009 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 7/23/2009 at 7:42:24 AM. Contact: ###-####. hard ceilings and 1 wall in rest rm
|