Permanent Service | 7/31/2009 | 7/31/2009 | 7/31/2009 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Bryan p/s o/h new ok
|
Final | 7/31/2009 | 7/31/2009 | 7/31/2009 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Bryan Atkins
|
Final | 7/30/2009 | 7/31/2009 | 7/31/2009 | A | CANC |
Jack Frank
|
|
|
Customer agreed to put in new panel.
**This should be for a PERMANENT service, NOT TEMP** Phone #: ###-#### Internet Inspection Request from: Bryan Atkins Inspection cancelled from web by: Bryan Atkins
|
Final | 7/30/2009 | 7/31/2009 | 7/30/2009 | A | CANC |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Bryan Atkins Inspection cancelled from web by: Bryan Atkins
|
Final | 7/22/2009 | 7/23/2009 | 7/23/2009 | A | FAIL |
Bob Reichert
|
|
|
Please call Bryan prior to inspection Phone #: ###-#### Internet Inspection Request from: Bryan Atkins called contractor, left correction notice, NEC 406.8(B) receptacles shall be listed weather resistant type, 250.53(B) electrodes shall be not less than 6' apart, 250.53(G) electrodes shall be at least 8' long and deep, 312.5 conductors entering enclosure shall be protected from abrasion by approved method, 110.12(B) there shall be no broken parts, damaged hasp, receptacles, BCC there shall be no foreign material (bee hives) inside enclosure, shall permit for correct use- t/s or p/s, job id sticker shall be posted, fee due
|