Final | 9/17/2009 | 9/17/2009 | 9/17/2009 | P | CANC |
Bob Reichert
|
|
|
Jared Phone #: ###-#### done in am 9-17-09
|
Final | 9/17/2009 | 9/17/2009 | 9/17/2009 | A | PASS |
Bob Reichert
|
|
|
corrections made, ok to final, no card to sign
|
Final | 9/16/2009 | 9/16/2009 | 9/16/2009 | P | FAIL |
Bob Reichert
|
|
|
Jared-please call at least 30 mins prior for access Phone #: ###-#### caled, left correction notice, NEC 110.3(B) listed equipment shall be installed per instructions, 110.22(A) each disconnect shall be legibly labelled and suitable for environment, 406.4 receptacles shall be securely mounted
|
Final | 9/10/2009 | 9/11/2009 | 9/11/2009 | P | CANC |
Bob Reichert
|
|
|
jared - units 16 and 17 Phone #: ###-#### talked with contractor, owner allowed power to be turned off and no re-connect requested, will call back when ready,
|
Electrical Rough-In | 7/28/2009 | 7/28/2009 | 7/28/2009 | P | PASS |
Bob Reichert
|
|
|
lars Phone #: ###-#### corrections made, ric 2 east units only ok
|
Electrical Rough-In | 7/27/2009 | 7/28/2009 | 7/28/2009 | A | FAIL |
Bob Reichert
|
|
|
Lars Phone #: ###-#### called, left correction notice, NEC 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing members or use steel plates for protection, 210.52(A)(1) receptacles shall be spaced such that no point along wall line is over 6' from an outlet, 250.24(A) grounded conductor shall be connected to grounding electrode at service only, 348.30 fmc shall be securely fastened within 12" of box, BCC shall provide boxes for nm termination points, no violations shall be retained
|