Final | 8/31/2009 | 9/1/2009 | 9/1/2009 | P | PASS |
Bob Reichert
|
|
|
Contact: Paul Cushing Phone #: ###-#### Internet Inspection Request from: Deb Gooden corrections made, ok to final, signed occupancy card
|
Final | 8/28/2009 | 8/31/2009 | 8/31/2009 | A | FAIL |
Bob Reichert
|
|
|
Contact is Darby Talbot Phone #: ###-#### Internet Inspection Request from: Shelli Daylong met contractor, left correction notice, NEC 210.63 shall provide 125v, single phase 15 or 20a 5receptacle within 25' of hvac equipment, 210.62 shall provide showroom receptacles, 210.8(B)(5) receptacles within 6' of sink shall be gfci protected, 408.4 panel schedules shall be clear, concise and direct, 400.8 shall not use cord for substitue for fixed wiring of structure, no esc this project
|
Electrical Rough-In | 7/30/2009 | 7/30/2009 | 7/30/2009 | P | PASS |
Bob Reichert
|
|
|
Contact Paul Cushing Phone #: ###-#### Internet Inspection Request from: Shelli Daylong corrections made, ric ok, no esc this project
|
Electrical Rough-In | 7/29/2009 | 7/30/2009 | 7/30/2009 | A | FAIL |
Bob Reichert
|
|
|
Contact: Paul Cushing Phone #: ###-#### Internet Inspection Request from: Deb Gooden called contractor, told to secure mc cable within 12" of box emt 3' and 10', all make-up shall be done, group permits, call back when done, no esc this project
|