Final | 6/17/2010 | 6/17/2010 | 6/17/2010 | P | PASS |
Jack Frank
|
|
|
Inspection requested from web by: Brandon Blackham Phone #: ###-####
|
Final | 6/9/2010 | 6/9/2010 | 6/9/2010 | P | FAIL |
Bob Reichert
|
|
|
Inspection requested from web by: Brandon Blackham Phone #: ###-#### called, left message, left correction notice, NEC210.52(C)(1) receptace shall be nmounted within 24" of sink edge, 210.52(A)(2)(3) shall provide convenience receptacles below bar type counter, 314.20 shall provide cover for box in utility room, NOTE corrections shall be made within 5 working days or further action will be taken
|
Final | 9/14/2009 | 9/15/2009 | 9/14/2009 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham Inspection cancelled from web by: Brandon Blackham
|
Rough-In Permanent Service | 8/4/2009 | 8/4/2009 | 8/4/2009 | A | PASS |
Bob Reichert
|
|
|
Call for code to lock box Phone #: ###-#### Internet Inspection Request from: Brandon Blackham called contractor, ric ok, p/s o/h n ok
|