Permit Information
Permit NumberELE09-01457
StatusFinaled
Name SMART ELECTRIC
Site Address 2978 E SWEETWATER DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/11/20099/11/20099/11/2009PPASS
DetailsBob Reichert
alan Phone #: ###-#### called contractor, ok to final
Electrical Rough-In8/25/20098/27/20098/27/2009APASS
DetailsBob Reichert
Allen--Please call at least 30 mins prior to inspection--Inspection is for pool pipes Phone #: ###-#### corrections made, ok to cover u/g only
Electrical Rough-In8/24/20098/25/20098/25/2009AFAIL
DetailsBob Reichert
Allen--conduit for pool Phone #: ###-#### called, left correction notice, NEC 300.5 minimum burial depth shall be 18" except under 4" concrete, 352.36 there shall not more than 360 degrees total bends in raceway, shall use schedule 80 where subject to physical damage
Electrical Rough-In8/24/20098/24/20098/24/2009PFAIL
DetailsBob Reichert
Alan Phone #: ###-#### called, left correction notice, BCC all u/g shall be inspected before cover, fee due
Electrical Rough-In8/10/20098/10/20098/10/2009PPART
DetailsDoug A Poedy
Alan Phone #: ###-####. Ok to cover pool bonding.