ELE-Aging Inspection | 8/26/2010 | 8/26/2010 | 8/26/2010 | | CANC |
Jack Frank
|
|
|
|
DOC - Permit Expired | 8/26/2010 | 8/26/2010 | 8/26/2010 | P | PASS |
Jack Frank
|
|
|
|
Electrical Rough-In | 9/11/2009 | 9/11/2009 | 9/11/2009 | P | PASS |
Mike Kinnear
|
|
|
Jay Phone #: ###-#### ok cover ri
|
Final | 9/10/2009 | 9/11/2009 | 9/11/2009 | A | PART |
Jack Frank
|
|
|
jay Phone #: ###-#### contr needs to secure permit for hot tub, and other work done before final ok
|
Permanent Service | 8/21/2009 | 8/21/2009 | 8/21/2009 | P | PASS |
Jack Frank
|
|
|
jay Phone #: ###-#### p/s o/h rec. ok
|
Conference | 8/18/2009 | 8/19/2009 | 8/19/2009 | A | DONE |
Bob Reichert
|
|
|
Jay Phone #: ###-#### met contractor and owner, reviewed service change and sub-panels, inspection request, left correction for owner NEC 110.26 sufficient access and working space shall be provided and maintained about all electrical equipment, 230.70(A)(!) service disconnecting means shall be installed at a readily accessible location outside of a building, 230.6(2) conductors shall be considered outside of building where installed in raceway encased in not less than 2" of concrete- owner asked for tis correction notice for his own sake, talked about derating conductors, conduit fill, j-boxes, grounding, mast height, no esc this project
|