Final | 8/24/2009 | 8/25/2009 | 8/25/2009 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ron Zimmerman
|
Temporary Service | 8/25/2009 | 8/25/2009 | 8/25/2009 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ron Zimmerman t/s u/g new ok
|
Temporary Service | 8/24/2009 | 8/24/2009 | 8/24/2009 | P | FAIL |
Bob Reichert
|
|
|
Ron Phone #: ###-#### called, left correction notice, NEC 110.12(B) there shall be no parts that are damaged- cable is cut, 250.53(G) rod electrode upper end shall be flush with or below ground, 408.4 shall provide circuit directory, 590.6(B)(1) shall provide gfci protection for personnel or (2) assured grounding program, 400.5(A) shall provide minimum #4 cord cable and type hard usage and type "W" ratings for wet locations, BCC shall post job id sticker, fee due
|