Permit Information
Permit NumberELE09-01566
StatusFinaled
Name BLACKHAM ELECTRIC
Site Address 2113 S MYERS PL
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Temporary Service8/25/20098/26/20098/26/2009APASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham corrections made, t/s u/g n ok
Temporary Service8/24/20098/25/20098/25/2009AFAIL
DetailsBob Reichert
Brandon Phone #: ###-#### called, left correction notice, NEC 250.24(B) shall provide unspliced main bonding jumper to connect the equipment grounding conductor and the service disconnect enclosure to the grounded conductor per 250.28, 406.8(B) 15 and 20 amp receptacles shall be listed weather resistant type, fee due