Final | 9/24/2013 | 9/24/2013 | 9/24/2013 | P | PASS |
Daryl DeGrange
|
|
|
job completed by electrical contractor ELE13-02613
|
ELE-Aging Inspection | 9/19/2013 | 9/19/2013 | 9/19/2013 | | DONE |
Daryl DeGrange
|
|
|
Electrical contractor taking over job
|
ELE-Aging Inspection | 6/19/2013 | 6/19/2013 | 6/27/2013 | | DONE |
Daryl DeGrange
|
|
|
still under construction
|
Final | 6/20/2013 | 6/27/2013 | 6/27/2013 | P | FAIL |
Daryl DeGrange
|
|
|
eric please call 30 min before going out as he wants to be there Phone #: ###-#### Did walk through with landlord, Landlord made complete of corrections. WR,TR common trip breakers, AFCI, clearance for service panel, Labeled disconnect switch in garage. Landlord agreed to hire Idaho licenced contractor to complete work.
|
ELE-Aging Inspection | 1/23/2013 | 1/23/2013 | 1/25/2013 | | DONE |
Daryl DeGrange
|
|
|
still under construction
|
ELE-Aging Inspection | 10/15/2012 | 10/15/2012 | 10/17/2012 | | DONE |
Daryl DeGrange
|
|
|
talked with Mr. Holtz briefly about his ageing electrical permit, He would check-in to get it and call back.
|
ELE-Aging Inspection | 7/5/2012 | 7/5/2012 | 7/11/2012 | | CANC |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 4/5/2012 | 4/5/2012 | 4/10/2012 | | DONE |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 1/5/2012 | 1/5/2012 | 1/9/2012 | | CANC |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 10/3/2011 | 10/3/2011 | 10/6/2011 | | DONE |
Jack Frank
|
|
|
waiting for owner to call for reinspection
|
ELE-Aging Inspection | 6/6/2011 | 6/6/2011 | 6/10/2011 | | CANC |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 3/7/2011 | 3/7/2011 | 3/14/2011 | | DONE |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 1/3/2011 | 1/3/2011 | 1/10/2011 | | CANC |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 11/3/2010 | 11/3/2010 | 11/10/2010 | | CANC |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 9/3/2010 | 9/3/2010 | 9/10/2010 | | CANC |
Jack Frank
|
|
|
|
Final | 8/28/2009 | 8/31/2009 | 8/31/2009 | A | FAIL |
Bob Reichert
|
|
|
TED Phone #: ###-#### called, left correction notice, NEC 250.94 shall provide intersystem bonding connection termination, 210.8(A) shall provide gfci protection for garage and outdoor receptacles, 110.26(A) shall provide workspace and clear space at panel and meter,210.52(C)(1) shall provide countertop receptacles such that no point is over 24" from receptacle 406.11 all receptacles shall be tamper-resistant 406.4(D) receptacle faces shall be flush with or project from faceplates, 422.10(A) a/c branch circuit shall not exceed listed requirements for overcurrent protection, 110.22 shall label disconnects, 225.31 shall provide disconnect at garage per 225.36, BCC shall install dishwasher for final, shall see u/g at garage
|
Final | 8/27/2009 | 8/27/2009 | 8/27/2009 | P | FAIL |
Jack Frank
|
|
|
Eric Phone #: ###-#### trench covered before inspection talked with permit holder
|