Final | 1/5/2010 | 1/5/2010 | 1/5/2010 | P | PASS |
Bob Reichert
|
|
|
Please call Rowdy for conference or to have him meet you 45 minutes ahead so he can meet you at the job site. Inspection on work station tables. Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe called, corrections made, ok to final, no esc this project
|
Conference | 12/15/2009 | 12/15/2009 | 12/15/2009 | P | DONE |
Bob Reichert
|
|
|
Rowdy ###-#### met contractor, most corrections done, told him that if he re-wires equipment to code, would pass inspection, otherwise he will need a field evaluation. Told that could not cord and plug as now done since equipment bolted to floor, no esc this project
|
Final | 11/11/2009 | 11/12/2009 | 11/12/2009 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe called,left message, left correction notice, NEC 330.30(B) mc cable shall be secured within 12" of termination, 358.12(5) shall not use emt as support for other equipment-mc cable, 110.3 all equipment shall be listed, BCC-4-05-33(A),(B) all equipment shall be listed by a nationally recognized testing laboratory, Note: corrections shall be made within 2 weeks or further action will be taken- such as removal of power, no esc this project
|
ELE-Aging Inspection | 10/27/2009 | 10/27/2009 | 11/3/2009 | | DONE |
Bob Reichert
|
|
|
no activity, suc, no esc this project
|
Electrical Rough-In | 8/26/2009 | 8/27/2009 | 8/27/2009 | P | PASS |
Bob Reichert
|
|
|
Rowdy Phone #: ###-#### ric ok, no esc this project
|
Permanent Service | 8/27/2009 | 8/27/2009 | 8/27/2009 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/27/2009 at 6:23:31 AM. Contact: ###-####. p/s o/h n ok, no esc this project, check labelling at final
|