Final | 11/9/2009 | 11/10/2009 | 11/10/2009 | A | PASS |
Bob Reichert
|
|
|
Any questions please call,garage code 1234 or 4321, thanks! TW. Phone #: ###-#### Internet Inspection Request from: Stephen Kren ok to final
|
Electrical Rough-In | 9/10/2009 | 9/11/2009 | 9/11/2009 | A | PASS |
Bob Reichert
|
|
|
corrections fixed. Phone #: ###-#### Internet Inspection Request from: Stephen Kren corrections made, ric ok
|
Rough-In Permanent Service | 9/9/2009 | 9/10/2009 | 9/10/2009 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Stephen Kren see p/s and ri
|
Permanent Service | 9/10/2009 | 9/10/2009 | 9/10/2009 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Stephen Kren p/s u/g n ok
|
Electrical Rough-In | 9/10/2009 | 9/10/2009 | 9/10/2009 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Stephen Kren called, left correction notice, NEC 110.3(A)(B) and BCC 4-05-33(A)(B) shall use listed or labelled equipment- #14 nm cable, NEC 210.52(A)(1)(2) shall install receptacles such that no point is over 6' along wall line from an outlet and also in 2' walls
|