Final | 11/12/2009 | 11/12/2009 | 11/12/2009 | P | PASS |
Bob Reichert
|
|
|
Tim Phone #: ###-#### ok to final
|
Electrical Rough-In | 9/23/2009 | 9/24/2009 | 9/24/2009 | A | PASS |
Bob Reichert
|
|
|
tim Phone #: ###-#### corrections made, ric ok
|
Conference | 9/23/2009 | 9/23/2009 | 9/23/2009 | P | CANC |
Bob Reichert
|
|
|
needed to look up phone number only
|
Electrical Rough-In | 9/23/2009 | 9/23/2009 | 9/23/2009 | P | FAIL |
Bob Reichert
|
|
|
tim Phone #: ###-#### called, left correction notice, NEC 300.14 there shall be at least 6" free conductor length at each box, 300.4(A) shall provide steel plate if edge of bored hole is less than 1 1/4" from edge of framing member, 250.86 metal enclosures shall be grounded and connected to equipment grounding conductor, BCC shall install mud rings as required before cover
|