Temporary Service | 10/5/2009 | 10/6/2009 | 10/6/2009 | A | PASS |
Bob Reichert
|
|
|
Corrections have been made Phone #: ###-#### Internet Inspection Request from: Rhonda Yoast corrections made, t/s u/g n ok, no esc this project
|
Temporary Service | 10/2/2009 | 10/2/2009 | 10/2/2009 | P | FAIL |
Bob Reichert
|
|
|
BILL Phone #: ###-#### called, left correction notice, NEC 406.8(B) 15 and 20 A receptacles shall be listed weather resistant type, 200.6(A) shall not use white color for phase wire, 110.3(B) listed equipment shall be installed in accordance with instructions - breakers, 110.9 equipment shall have interrupting rating sufficient for available cirrent, BCC gec shall not touch meter terminal
|